Panel Connection - Serial

Manufacturer Europlex
Model 3GS
Panel Firmware Range V.2.09 and above
UDL Package Panelman
Cable required? No
MCM or Serial Connection Serial
Panel Profile Europlex3GS
Panel Bus Connection RS232
Technical Notes There is no line fault indication through the panel bus to the keypad so the SPT outputs for line fault will be required.

Cable Connection

WebWay SPT Panel
232 R TX2
232T RX2
RTN 0V

SPT Connections

SPT Connections

Panel Connection

Panel Connection

Panel Programming

  • Once in Engineer mode navigate to Data Format
  • Set the Port 2 rate to: Port 2 19200 E,8,1
  • Click here for Remote Manager and Upload / Download settings

Remote Access Programming

  • Go to ‘set up downloading’
  • Select download by (WebWayOne)
  • Select poll timeout <10>
  • Select modem init timeout <060>
  • Select rings to answer <1>
  • Select comm. Tx timeout <030>
  • Select ARMPC telephone number (not required)
  • Select program PCs <1>
  • Select modem telephone number (not required)
  • Select signal alarms (No)
  • Select signal faults (No)
  • Select signal set/unset (No)
  • Select signal access code (No)
  • Select password (optional UDL password)
  • Select redials <03>

  • Select time out <00>
  • Select stop on success (No)
  • Select dial mode (retry same)
  • Exit engineering mode and save the configuration