Panel Connection - MCM

Manufacturer UTC
Model ATS
Version Advanced
Panel Firmware Range 023.023.0123 +
Cable required? N/A
MCM, Serial or Peripheral Peripheral
Panel Profile ATS-Adv-Digi
Panel Bus Connection None
Technical Notes Please see below

Cable Connection

PANEL MCM Module on SPT
A (Digi) A (MCM)
B (Digi) B (MCM)

Panel Connection

Panel Programming

  • Enter : Installer Mode (Engineer)
  • Select: 9>Dialler menu
  • Enter: 1> CS
  • Enter: 01> CS 1
  • Set: CS name [CS 1]
  • Enter: 2>‘Transm Path’ [PSTN]
  • Enter 3>‘Protocol’
  • Set: (X)SIA’
  • Enter 4>Phone [987654321]
  • Enter 5>‘Accounts’ menu
  • Select: ‘Area ‘1’ with [account numbers]
  • Select: ‘Area ‘2’ with [account numbers OR blank]
  • Select: ‘Area ‘3’ with [account numbers OR blank]
  • Select: ‘Area ‘4’ with [account numbers OR blank]
  • Enter 6>‘Mode’

  • Set: Primary CS’
  • Enter 7> retry count [10]
  • Enter 8>‘Protocol opt’
  • Set: ‘(X)SIA’
  • Set ‘Area Modifier’ to ‘[ON]’
  • Set ‘Name Chars’ to ‘[30]’
  • Set ‘Event Number’ to ‘[3 digits]’
  • Set ‘Subev codeing’ to ‘[Decimal]’
  • Set ‘SIA Frequency’ to ‘[Bell]’
  • Go back to ‘Dialler’ menu level
  • Enter 3>‘Path Options’
  • Enter 1>‘PSTN’
  • Enter 2>‘Line Fault’ menu and select option ‘[No]’

  • Go back to ‘Path Options’ menu level.
  • Enter 4>IP (If present)
  • Enter ‘Line Fault’ menu and select option ‘[No]’
  • Enter 4>‘PC Conn’ menu
  • Select 1>‘PC Conn 1’
  • Set 2>‘Trans Path’ to ‘PSTN’
  • Set 3>‘Modem Protocol’ to ‘V22’
  • Set 4>‘Phone Number’ to ‘None’ or blank
  • Set 5>‘Retry Timeout’ to ‘3’
  • Set 2>‘PC Callback’ to ‘Off’
  • Set 3>‘Encrypt Key 1’ as required
  • Set 4>‘Encrypt Key 2’ as required
  • Set 5>‘Listening Port’ to ‘n/a or None’
  • Set 6>‘Panel ID’ to ‘None’
  • Enter ‘Path Options’ menu
  • Enter ‘PSTN’
  • Set ‘Name’ to ‘PSTN’
  • Set ‘Line Fault’ as required
  • Set ‘Line Fault Delay’ to ‘0’
  • Set ‘Transmission Path’ to ‘PSTN’
  • Set ‘Dial Tone’ to ‘UK’
  • Set ‘Dialling’ to ‘DTMF’
  • Set ‘Ring Count’ to ‘1’
  • Set ‘Encryption’ to ‘No’

  • Exit Installer / Engineer Mode
  • Note: This may require a full panel and SPT reboot.

Troubleshooting

  • To enter engineer mod, access must be allows via a setting in User mode.
  • After defaulting the panel, the panel will ask questions on power up.
  • User Code : Menu 8:2:1 - Need Acc [YES]
  • Eng Code : Menu 8: Sys Opt > 7: Panel & AB Opts > 9: Remote Config - YES