WebWayWorld Logo 2018

 

Panel Connection - RS232

Manufacturer UTC
Model ATS
Version Advisor Master
Panel Firmware Range Please refer to panel manufacturer
Cable required? No
MCM or Serial Serial
Panel Profile ATS4000
Panel Bus Connection RS232
Technical Notes Please see below

Cable Connection

Panel SPT Colour
TXD 232 R Red Wire
RXD 232 T Green Wire

GND
----
CTS*

RTN
----
A+ (Power)

Blue Wire
----
Orange Wire

Panel Connection

SPT connection

SPT connection

Panel connection

Panel connection

Panel Programming

  • Menu 9 - Communications menu
  • PBX [not set]
  • MSN [not set]
  • DT Detection [UK]
  • DTMF tone dialling [Yes]
  • Enable PSTN line fault monitor [No]
  • Monitor service tones [No]
  • 3 digit SIA extensions [Yes]
  • ISDN point to point [No]
  • Enable ISDN line fault monitor [No]
  • 3 digit SIA extensions [Yes]
  • 200 baud reverse area open/close [No]
  • X25 TEI value [2]
  • Audio listen in time [180]
  • Audio listen in frame time [30]
  • Report mains fault [Yes]
  • Report line fault [Yes]
  • Enable GSM line fault monitor [No]
  • Central station
  • CS No <1> Enter
  • Format No: (Option 7)
  • Ph1
  • Ph2 [not set]
  • Acc No: system account number
  • Acc No: area 1 account number
  • Bell modem: [Yes]
  • Dual reporting [No]
  • Listen in [No]
  • Disable reporting inhibits [No]
  • Reserved [No]
  • XSIA Max characters [30]
  • X25 account code not important
  • Conn type (Option 4)
  • suppress FTC for voice reporting [No]
  • Retry count [10]
  • SIA Area Modifier [Yes]
  • X25 D-bit [No]
  • Mains Fail Reporting delay [30]
  • Enable IP Line Fault Monitor [No]
  • AWDGP reporting codes for IMQ [No]

  • Menu 29 - Computer Connections menu
  • Enable Remote Up\Download [Yes]
  • Up/Download if any area armed [Yes]
  • Enable Remote Control [Yes or No]
  • Remote Control if any area armed
  • Use modem Init [No]
  • Report Alarms to computer [No]
  • Report Access to computer [No]
  • Cmp, Cbk, Srv
  • Computer Address [0001]
  • Security Password [0000000000]
  • Security Attempts [255]
  • Number of Rings [1]
  • Number of Calls [0]
  • Answer Machine [No]
  • Reserved [No]
  • Bell Modem [No]
  • Conn Type * (Option 4)
  • PC connections authorised [No]

Troubleshooting

  • Note for ATS 2000 panels set the connection type here as PSTN. Rather than serial interface. The connection type in menu 9 needs to remain as Universal Interface.
  • *Please note without 12V to the CTS connection on the serial interface the serial board will not operate.

UDL information for this item can be found here:

Support

Knowledge Base

Panel Guides

Downloads

FAQs